| |
|
|
| |
How can I use the Summation Function in PTW ? |
|
| |
The Protective Device Function in PTW v6.5 contains new features for modeling additional functions, such as
summation, that can be utilized in Arc Flash Evaluation.
The following provides a brief description of implemented concept for the summation function, how it can be
used, and how to apply it in a study. |
|
| |
General Implemented Concept |
|
| |
1. The summation function in PTW is similar to a bus differential which can sum up the SC contribution
currents vectors (magnitude and angle) caused by a fault and passed through multiple devices already
modeled in the connected branches to the fault location. |
|
| |
2. Since the actual CTs for sensing and the conversion of the fault currents are not yet available, the protective
devices available in each branch will act in place of the CTs and the program will internally account for the
SC current summation. |
|
| |
3. The actual characteristics of the bus differential relay cannot currently be modeled in Captor. However, a
generic TCC representing any adjustable pickup and delay can be used instead to represent the trip time for
the fault. |
|
| |
4. Based on the above, a protective device is needed to be inserted in each of the branches connected to the
bus as the location of fault to define the protected zone. Every device type needs to be set as Summation
through the Function button in Captor or the Component Editor and linked to the library to represent the
generic TCC of the device. |
|
| |
The following example will better describe the use and application of the summation function. |
|
| |
|
|
| |
Example |
|
| |
Figures 1 and 2 represent a sample dual source distribution system containing only the phase Over Current Type
Function while Figure 3 displays the arc flash results for the switchgear bus (BUS-SWG) connecting the
generators and motor loads without any summation function or bus differential. |
|
| |
The following steps can be used to add summation function to the existing overcurrent phase function of the
PD-GEN-1 relay. This relay will be used together with all other relays (PD-GEN-2, PD-1, and PD-2) as the
reference for the sensed current by each of these CTs. |
|
| |
 |
|
| |
Figure 1 |
|
| |
 |
|
| |
Figure 2 |
|
| |
 |
|
| |
Figure 3 |
|
| |
1. Select the PD-GEN-1 device in the Captor TCC drwing (Figure 4) then click the Function button to display
the Protection Functions. |
|
| |
 |
|
| |
Figure 4 |
|
| |
2. Click the New button and type in Summation under the Function Name column. Select Summation from
the Type pull-down menu (Figure 5). |
|
| |
 |
|
| |
Figure 5 |
|
| |
3. The window for “Summation of Current from Selected Devices” will prompt for the selection of the
protective devices as the reference CTs. An additional option is provided to select these devices from the
TCC associated one-line drawing or from all of the devices in the project (Figure 6). |
|
| |
 |
|
| |
Figure 6 |
|
| |
4. Select and check the box for PD-GEN-1, PD-GEN-2, PD-1, and PD-2 as sensing devices. Note that there is
a +/- drop down menu for each device to reverse the direction of the sensed current. In other words, it will
add a 180 deg to the phase angle of the sensed current vector. Leave the +/- drop-down menu as “+” and
click OK to have the referenced device currents summed and displayed under the Summation/Direction
column (Figure 6 and 7). |
|
| |
 |
|
| |
Figure 7 |
|
| |
5. Note that the check box for “Used in Arc Flash” is not available for the newly created differential function
because no TCC curve from the library is assigned to it at this point. Click OK to return to the Captor TCC
screen to link this function to a model from the library. |
|
| |
6. Once the summation is displayed on top of the Functions button, click the Library button to select a generic
model for this differential function, similar to the device in Figure 8. Click Apply and Close to review the
TCC of the new differential function in Captor. |
|
| |
7. Note that the function names (Phase or Summation) are now added at the end of the PD-GEN-1 device
name (Figure 9). |
|
| |
 |
|
| |
Figure 8 |
|
| |
 |
|
| |
Figure 9 |
|
| |
8. Click the Function button again to confirm that the “Used in Arc Flash” is now available for the summation
function as well. Check this box to use the summation function in Arc Flash.
Note that the box in front of Phase is automatically unchecked (Figure 10). Now click OK. |
|
| |
 |
|
| |
Figure 10 |
|
| |
9. Repeat steps 1 through 8 above for all for other devices that are expected to isolate the protected zone.
They would be PD-GEN-2, PD-1, and PD-2 in our sample case. |
|
| |
10. Select BUS-SWG from the one-line drawing. Right-click and choose Go To/Find > Go To Arc Flash to
analyze the study results for the bus which is within the protection zone of summation relays (Figure 11). |
|
| |
11. As shown in Figure 12, the incident energy and required PPE has been reduced due to 0.05 sec trip time of
the summation functions set at this delay time. |
|
| |
12. Note that in the sample case, the addition of summation function to the motor protection devices (PD-1 and
PD-2) will not change the arc flash study results for BUS-SWGC. This is due to having a total of 0.083 sec
(5 cycle) duration for the contribution of the motors that is less than total clearing time of summation
function for these devices
PD-1 and PD-2 Summation Function Total Clearing Time = 0.05 + 0.083 = 0.135 sec > 0.083 sec (5 cycle) |
|
| |
 |
|
| |
Figure 11 |
|
| |
 |
|
| |
Figure 12 |
|
| |
|
|