NEC 2008 Section 110.16 requires an arc-flash warning label on equipment. Is
this a field-applied label or does equipment manufacturers provide and affix
the label when they build the equipment in the factory?
Answer:
In the 2008 NEC Section 110.16 requires that the equipment shall be field marked to
warn qualified persons of potential electric arc flash hazards. This is not a label
applied by the manufacturer of the equipment. It is unknown how the equipment will
be used in the field.
|