The primary-side phase A and C relays would see 0.50 A p.u. fault current and the phase B relay would see 1.0 A p.u. fault current on a 3-Ø primary fault current base, figure 3.

Line-to-Line-Ground (LLG) Secondary Fault
The primary-side phase A and C relays would see 0.58 A p.u. fault current and the phase B relay would see 1.0 A p.u. fault current on a 3-Ø primary fault current base, figure 4.

Transformer secondaries were faulted and primary currents were calculated for each fault type and summarized in Table 2 for winding configurations listed in Table 1.
Table 2 Fault Current Summary Table

1. Shifting of the damage curve is dependent upon the amp rating of the NGR relative to the transformer primary-side FLA. Shifting is To Be Determined by the engineer on a case by case basis. For a sample case study see Example 3.
Example 1
Plot the damage curve and set a primary-side 50/51 relay to protect a 1000kVA, 65ºC, 4160-480/277V, Δ-YG, oil-filled, substation transformer with an impedance of 6.0%.
Consider secondary 3-Ø faults only when setting the primary-side 50/51 relay to protect the transformer during through-faults.
Solution
The protection is met based on the criteria given, see Figure 5.
Now examine the protection provided by the 50/51 relay shown in figure 1 for faults of all types using Table 1. For a secondary LL fault the primary relays in phases A and C would only see 50% of the fault current they would otherwise see for a 3-Ø fault. This is not a problem though because the B-phase relay would see 100% current, and the transformer would be protected.
The LLG fault is similar to the LL fault accept that the relays in phases A and C would see 58% current. But again the B-phase relay would see 100% current, so the transformer would be protected.
However for the SLG fault case, the A and C-phase relays would see 58% current with no current flowing in the B-phase! In order to evaluate the through-fault current protection afforded by the relays for a secondary SLG fault, the damage curve of Figure 5 would have to be shifted 58% to the left. It is common practice to show both damage curves on the TCC. After shifting it becomes apparent that the original relay settings are inadequate, see Figure 6.
Example 2
Repeat Example 1 but now consider secondary faults of all types when setting the primary-side 50/51 relay to protect the transformer during through-faults.
Solution
The protection is met based on the criteria given, see Figure 7.

Fig. 5 Example 1 Though-Fault Current Protection (3-Ø Fault Only)

Fig. 6 Example 1 Though-Fault Current Protection (All Faults)

Fig. 7 Example 2 Though-Fault Current Protection (All Faults)
Example 3
Consider the case of a 5000kVA, 65ºC, 13800-4160/2400V, Δ-YG, oil-filled, substation transformer with an impedance of 6.0%. The secondary neutral terminal is grounded through a 400A NGR.
Solution
Step 1 Determine the primary FLA
FLA PRI = 5000kVA / (1.732 x 13.8kV) = 209A
Step 2 Determine the primary-side current distribution for a secondary-side SLG fault
I SLG SEC = 400 amps
I FAULT PRI = 0.58 x 400 amps (4160V / 13800V) = 69 amps
Step 3 Determine the relationship between I FAULT PRI and FLA PRI
I FAULT PRI = 69 < FLA PRI = 209A
Conclusions
- No shifting is required, see Figure 8.
- The relay is not capable of distinguishing between a secondary-side SLG fault and an increase in load
- In this case it is common practice to protect the transformer using a 51G relay fed from a current transformer mounted in the secondary neutral bushing.
- If the transformer protection system includes a 51G relay there is no need to perform this calculation.

Fig. 8 Example 3 Though-Fault Current Protection (Δ-YRG)
References
- Other Application Guides offered by SKM Systems Analysis at www.skm.com
The latest revision of:
- IEEE Std C57.12.00, IEEE Standard General Requirements for Liquid-Immersed Distribution, Power and Regulating Transformers
- IEEE Std C57.12.01, IEEE Standard General Requirements for Dry-Type Distribution and Power Transformers Including Those with Solid-Cast and/or Resin-Encapsulated Windings
- IEEE Std C37.91, IEEE Guide for Protective Relay Applications to Power Transformers